Safety integrity level: |
SIL3 (IEC 61508) SILCL3 (EN 62061) |
Category: |
Category 4 (EN ISO 13849-1) |
Performance level: |
PL e (EN ISO 13849-1) |
PFHd: |
1.07 * 1E-09 (EN ISO 13849) |
TM (mission time): |
20 a (EN ISO 13849) |
Functions |
Restart interlock: |
Manual / automatic (configurable) |
External device monitoring (EDM): |
|
Differentiation between man and material (muting): |
|
Safe SICK device communication via EFI/SDL: |
- |
Flexi Link: |
- |
Flexi Line: |
- |
Automatic Configuration Recovery (ACR): |
- |
Mechanical data |
Dimensions (W x H x D): |
22.5 mm x 96.5 mm x 120.6 mm |
Weight: |
111 g (± 5 %) |
Electrical data |
Protection class: |
III (EN 61140) |
Type of voltage supply: |
PELV or SELV 1) |
Supply voltage Vs: |
24 V DC (16.8 V DC ... 30 V DC) |
Internal power consumption: |
≤ 2.5 W |
Overvoltage category: |
II (EN 61131-2) |
Switch-on time: |
≤ 18 s |
Interfaces |
System connection: |
System plug FX3-MPL000001 |
Connection type system plug: |
Screw-type terminals |
Number of EFI interfaces: |
0 |
Configuration and diagnostics interface: |
RS-232 |
Ambient data |
Enclosure rating terminals: |
IP 20 (EN 60529) |
Protection class housing: |
IP 40 (EN 60529) |
Ambient operating temperature: |
-25 °C ... 55 °C |
Storage temperature: |
-25 °C ... 70 °C |
Air humidity: |
10 % ... 95 %, non-condensing |
Climate conditions according to: |
EN 61131-2 (55 °C ambient operating temperature, 95% rel. humidity) |
Electromagnetic compatibility (EMC): |
Class A (EN 61000-6-2, EN 55011) |
Vibration resistance: |
1 g, 5 Hz ... 150 Hz (EN 60068-2-6) 3 g RMS, 10 Hz ... 500 Hz (EN 60068-2-64) |
Shock resistance (continuous shock): |
10 g, 16 ms (EN 60068-2-27) |
Shock resistance (single shock): |
30 g, 11 ms (EN 60068-2-27) |